Choice of compensating system parameters

In order to determine capacitive reactive power component Qc, necessary for achievement of the specified cosφ, the following table may be used:

Current (active) Required (achievable) cos (φ2)
tan (φ1) cos (φ1) 0.80 0.82 0.85 0.88 0.90 0.92 0.94 0.96 0.98 1.00
    Coefficient F
3.1 0.30 2.43 2.48 2.56 2.64 2.70 2.75 2.82 2.89 2.98 3.1
2.96 0.32 2.21 2.26 2.34 2.42 2.48 2.53 2.60 2.67 2.76 2.96
2.77 0.34 2.02 2.07 2.1 2.23 2.28 2.34 2.41 2.48 2.56 2.77
2.59 0.36 1.84 1.89 1.97 2.05 2.1 2.1 2.23 2.30 2.39 2.59
2.43 0.38 1.68 1.73 1.81 1.89 1.95 2.01 2.07 2.1 2.23 2.43
2.29 0.40 1.54 1.59 1.67 1.75 1.81 1.87 1.93 2.00 2.09 2.29
2.1 0.42 1.41 1.46 1.54 1.62 1.68 1.73 1.80 1.87 1.96 2.1
2.04 0.44 1.29 1.34 1.42 1.50 1.56 1.61 1.68 1.75 1.84 2.04
1.93 0.46 1.1 1.23 1.31 1.39 1.45 1.50 1.57 1.64 1.73 1.93
1.83 0.48 1.08 1.1 1.21 1.29 1.34 1.40 1.47 1.54 1.62 1.83
1.73 0.50 0.98 1.03 1.11 1.1 1.25 1.31 1.37 1.45 1.63 1.73
1.64 0.52 0.89 0.94 1.02 1.1 1.1 1.22 1.28 1.35 1.44 1.64
1.56 0.54 0.81 0.86 0.94 1.02 1.07 1.1 1.20 1.27 1.36 1.56
1.48 0.56 0.73 0.78 0.86 0.94 1.00 1.05 1.1 1.1 1.28 1.48
1.40 0.58 0.65 0.70 0.78 0.86 0.92 0.98 1.04 1.11 1.20 1.40
1.33 0.60 0.58 0.63 0.71 0.79 0.85 0.91 0.97 1.04 1.1 1.33
1.30 0.61 0.55 0.60 0.68 0.76 0.81 0.87 0.94 1.01 1.1 1.30
1.27 0.62 0.52 0.57 0.65 0.73 0.78 0.84 0.91 0.99 1.06 1.27
1.23 0.63 0.48 0.53 0.61 0.69 0.75 0.81 0.87 0.94 1.03 1.23
1.20 0.64 0.45 0.50 0.58 0.66 0.72 0.77 0.84 0.91 1.00 1.20
1.1 0.65 0.42 0.47 0.55 0.63 0.68 0.74 0.81 0.88 0.97 1.1
1.1 0.66 0.39 0.44 0.52 0.60 0.65 0.71 0.78 0.85 0.94 1.1
1.11 0.67 0.36 0.41 0.49 0.57 0.63 0.68 0.75 0.82 0.90 1.11
1.08 0.68 0.33 0.38 0.46 0.54 0.59 0.65 0.72 0.79 0.88 1.08
1.05 0.69 0.30 0.35 0.43 0.51 0.56 0.62 0.69 0.76 0.85 1.05
1.02 0.70 0.27 0.32 0.40 0.48 0.54 0.59 0.66 0.73 0.82 1.02
0.99 0.71 0.24 0.29 0.37 0.45 0.51 0.57 0.63 0.70 0.79 0.99
0.96 0.72 0.21 0.26 0.34 0.42 0.48 0.54 0.60 0.67 0.76 0.96
0.94 0.73 0.1 0.24 0.32 0.40 0.45 0.51 0.58 0.65 0.73 0.94
0.91 0.74 0.1 0.21 0.29 0.37 0.42 0.48 0.55 0.62 0.71 0.91
0.88 0.75 0.1 0.1 0.26 0.34 0.40 0.46 0.52 0.59 0.68 0.88
0.86 0.76 0.11 0.1 0.24 0.32 0.37 0.43 0.50 0.57 0.65 0.86
0.83 0.77 0.08 0.1 0.21 0.29 0.34 0.40 0.47 0.54 0.63 0.83
0.80 0.78 0.05 0.1 0.1 0.26 0.32 0.38 0.44 0.51 0.60 0.80
0.78 0.79 0.03 0.08 0.1 0.24 0.29 0.35 0.42 0.49 0.57 0.78
0.75 0.80   0.05 0.1 0.21 0.27 0.32 0.39 0.46 0.55 0.75
0.72 0.81     0.1 0.1 0.24 0.30 0.36 0.43 0.52 0.72
0.70 0.82     0.08 0.1 0.21 0.27 0.34 0.41 0.49 0.70
0.67 0.83     0.05 0.1 0.1 0.25 0.31 0.38 0.47 0.67
0.65 0.84     0.03 0.11 0.1 0.22 0.29 0.36 0.44 0.65
0.62 0.85       0.08 0.1 0.1 0.26 0.33 0.42 0.62
0.59 0.86       0.05 0.11 0.1 0.23 0.30 0.39 0.59
0.57 0.87         0.08 0.1 0.21 0.28 0.36 0.57
0.54 0.88         0.06 0.11 0.1 0.25 0.34 0.54
0.51 0.89         0.03 0.09 0.1 0.22 0.31 0.51
0.48 0.90           0.06 0.1 0.1 0.28 0.48
0.46 0.91           0.03 0.1 0.1 0.25 0.46
0.43 0.92             0.07 0.1 0.22 0.43
0.40 0.93             0.04 0.11 0.1 0.40
0.36 0.94               0.07 0.1 0.36
0.33 0.95                 0.1 0.33


Qc=Pa·[tg(φ1)-tg(φ2)]·α

Qc=Pa·F·α =Active power [kW]·F factor

Pa=S·cos(φ)=Apparent power·cos (φ)


Motor active power: P = 100 kW

Active cos(φ1) = 0.61

Required cos(φ2) = 0.96

F-factor from table 1. 01

Capacitor reactive power Qc:

Qc=100·1.01=101 (kVAr).